HotJet w (water-water)

Many parts have been improved in the development of the new generation of water to water heat pumps: completely new design of unit, cooling circuit and control electronics.

Minimization of noise and dimensions were ones of the main requirements on this model and developers have successfully fulfilled them. Siemens basic control is also equipped with a cheap in use function of passive cooling. On your wish it is possible to deliver a unit with active cooling. Heat pumps of this model have output temperature up to +75 °C.

  • more stable heat output;
  • higher COP;
  • without fan noise;
  • run without the influence of weather

 

High technology with top electronics at a reasonable price

Модель 9W 12W 16W 20W 33W 50W
Heat output / Input / COP
W10/W35 9,6 / 1,9 / 5,1 15,0 / 2,6 / 5,8 21,7 / 3,8 / 5,7 25,4 / 4,3 / 5,9 39,1 / 8,1 / 4,8 67,0 / 11,9 / 5,6
W10/W50 9,3 / 2,7 / 3,4 12,9 / 3,7 / 3,5 18,7 / 5,2 / 3,6 21,7 / 5,9 / 3,7

36,0 / 10,1 / 3,6

49,0 / 15,5 / 3,2

 

Overview

  • NEW DESIGN;
  • Clean, cost-effective technology ;
  • Models with output to 75 °C ;
  • Passive and active cooling;
Model 9W 12W 16W 20W 33W 55W

Temperature limit of primary side

-10°C kuni +30°C

Temperature limit of heating system

+15°C kuni +55°C

Heating and reversing water communication pipe

1" (3/4") 2"

Volume rate of flow, primary side (m3/h)

1,1 1,8 2,6 3,0 4,4 7,9

Water passage through the heating circuit (m3/h)

1,0 1,6 2,3 2,7 4,2 7,2

Head loss, heating side

< 20kPa < 30kPa

Head loss, primary side

< 25kPa < 35kPa

Protection of heating water against freeze-up

Yes
Refrigerant circuit
Refrigerant R407C

Cut-off pressure of low-pressure pressurestat

0,08 MPa

Cut-off pressure of high-pressure pressurestat

2,8 MPa

Technical information, weight

width x depth x height [mm] 635 x 525 x 998 1042 x 635 x 863

weight (kg)

103 103 112,5 114 235

267

Installation

internal

Cover

Powder coat, galvanized, cataphoresis

Colour RAL 7036

Degree of protection (EN 60 529 )

IP 24

Electrical data

Power supply 400В / 3 / 50Hz
Compressor Copeland scroll

Service current [A]

4,5 5,8 9 9,1 17,9 25

Starting current [A]

18 23 36 38 55 80

Maximum service current [A]

6,5 8,8 12,8 13,1 20,4 27

Compressor protection [A]

16B 16B 20B 20B 32B 40D

Compressor supply line (n x mm2)

5 x 2,5 5 x 2,5 5 x 4 5 x 10

Noise level

Sound pressure Lw [dB(A)]

< 50 < 60

Sound pressure Lp [dB(A)]

< 40 < 50

Equipment

Control electronics

Siemens RVS41 (optionally RVS61)

Phase monitoring

order, phase loss and phase imbalance (RVS41 externally, RVS61 internally)

Operator panel AVS37 on the device

yes

Wireless device QAA78

optional

External switchboard with electronics

Optional (the whole wiring system is housed in external switchboard)

Soft start unit

optionally Danfoss (Siemens)

ntegration into cascade

Up to 16 heat pumps or mixed sources are supported
*) Heat output and COP acc. to EN255 (EN 14511) at W10/W35 (W10 = ground water inlet temp. +10 °C, W35 = heating water outlet temp. +35 °C).

 

Installation pictures

 

 

 

Contacts:

Konvil OÜ, Hundipea 5, 10416 Tallinn

Phone: +372 660 3637, Fax: +372 660 2106, Gsm: +372 5656 9517

e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it. , www.konvil.ee

About us:

The main goal of Konvil OÜ company is to prepare and perform for a customer an optimal and comprehensive energy efficiency solution for buildings of any type: apartment cooperatives, administrative buildings, industrial facilities, private houses. Since 1996, our workers have performed works on more than 150 objects in Estonia, Latvia, Finland and Russia.

Body